Operation Performance of Air Source Heat Pump System for Space Heating in Tianjin Operation Performance of Air Source Heat Pump System for Space Heating in Tianjin

Operation Performance of Air Source Heat Pump System for Space Heating in Tianjin

  • 期刊名字:天津大学学报(英文版)
  • 文件大小:
  • 论文作者:ZHAO Jun,CHEN Yan,QU Hang,LI X
  • 作者单位:School of Mechanical Engineering
  • 更新时间:2023-02-07
  • 下载次数:
论文简介

An air source heat pump system (ASHPS) used in an office building is set up and studied experimentally. Its operating performance in winter is evaluated based on test data and a comparative discussion is given on the effect of climate conditions and heating load ratio on the operation behavior.Then heating capacity variation caused by evaporator frosting is analyzed as well. Finally, the defrosting parameters and the technical feasibility are studied for a constant heating demand. The experimental results indicate that both the outlet water temperature drop and the system COP should be taken into account when setting defrosting parameters, and ASHPS is a viable technology for space heating and hotwater production in winter in Tianjin, which can maintain the room temperature above 19 ℃ when the outdoor temperature is -2 ℃.

论文截图
版权:如无特殊注明,文章转载自网络,侵权请联系cnmhg168#163.com删除!文件均为网友上传,仅供研究和学习使用,务必24小时内删除。