Online Partial Discharge Measurement of a High-voltage Direct Current Converter Wall-bushing

  • 期刊名字:高电压技术
  • 文件大小:
  • 论文作者:Nathan D. Jacob,William M. McD
  • 作者单位:Department of Electrical & Computer Engineering,Insulation Engineering & Testing Department
  • 更新时间:2022-11-24
  • 下载次数:
论文简介

An online partial discharge (PD) measurement performed on a high voltage direct current (HVDC) wall bushing successfully identified the presence of internal discharges. The wall bushing is a sulfur hexafluoride gas-insu- lated bushing, rated for 500 kV dc and terminated on a thyristor-controlled HVDC converter bridge. The measure- ment of PD within the HVDC station environment is particularly challenging due to the high levels of electromagnetic noise caused by thyristor switching events and external air-corona from the neighboring high-voltage equipment. An additional challenge is the "mixed" voltage stress on the bushing insulation, which has both ac and dc high-voltage components. There are also fast transients during the firing of thyristors in the HVDC conversion process that cause added stress to the insulation. As a result, the analysis and interpretation of PD data for HVDC equipment is more complex; PD pulses may occur in response to the ac, dc, or switching transient voltage stresses. In this paper, an on- line PD measurement strategy for noise filtering and isolation of PD sources within the bushing are discussed. The PD measurement data is plotted on a phase-resolved diagram where the line supply power cord voltage was used as a reference. The phase-resolved diagram appears to suggest that the fast transients, caused during switching, trigger some PD events. Measurements were also performed with the aid of a modern PD measurement instrument having noise separation capabilities. The findings from the online PD measurements are verified with physical evidence, found after the bushing was removed from service, suggested internal PD had occurred inside the bushing.

论文截图
版权:如无特殊注明,文章转载自网络,侵权请联系cnmhg168#163.com删除!文件均为网友上传,仅供研究和学习使用,务必24小时内删除。