Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal

Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal

  • 期刊名字:中国矿业大学学报(英文版)
  • 文件大小:
  • 论文作者:LI Xiao-bo,WANG Chong-lin
  • 作者单位:School of Information & Electrical Engineering
  • 更新时间:2022-09-17
  • 下载次数:
论文简介

When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and reliable run of the network.We first introduce a three-phase five-column arc suppression coil (TPFCASC) and discuss its autotracking compensation theory.Then we compare the single phase to ground fault of the coal mine distribution network with an open phase fault at the TPFCASC using the Thévenin theory, the symmetrical-component method and the complex sequence network respectively. The results show that, in both types of faults, zero-sequence voltage of the network will appear and the maximum magnitude of this zero-sequence voltage is different in both faults. Based on this situation, a protection for the open phase fault at the TPFCASC should be estab-lished.