IEC 60287-2-1-2015 电缆--电流定额的计算--第2-1部分:热阻--热阻计算 Electric cables – Calculation of the current rating – Part 2-1: Thermal resistance – Calculation of thermal resistance IEC 60287-2-1-2015 电缆--电流定额的计算--第2-1部分:热阻--热阻计算 Electric cables – Calculation of the current rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

IEC 60287-2-1-2015 电缆--电流定额的计算--第2-1部分:热阻--热阻计算 Electric cables – Calculation of the current rating – Part 2-1: Thermal resistance – Calculation of thermal resistance

  • 标准类别:
  • 标准大小:
  • 标准编号:IEC 60287-2-1-2015
  • 标准状态:现行
  • 更新时间:2023-05-01
  • 下载次数:
标准简介

This part of IEC 60287 is solely applicable to the conditions of steady-state operation of
cables at all alternating voltages, and direct voltages up to 5 kV, buried directly in the ground,
in ducts, in troughs or in steel pipes, both with and without partial drying-out of the soil, as
well as cables in air. The term "steady state" is intended to mean a continuous constant
current (100 % load factor) just sufficient to produce asymptotically the maximum conductor
temperature, the surrounding ambient conditions being assumed constant.
This part of IEC 60287 provides formulae for thermal resistance.
The formulae given are essentially literal and designedly leave open the selection of certain
important parameters. These may be divided into three groups:
– parameters related to construction of a cable (for example, thermal resistivity of insulating
material) for which representative values have been selected based on published work;
– parameters related to the surrounding conditions which may vary widely, the selection of
which depends on the country in which the cables are used or are to be used;
– parameters which result from an agreement between manufacturer and user and which
involve a margin for security of service (for example, maximum conductor temperature).
Equations given in this part of IEC 60287 for calculating the external thermal resistance of a
cable buried directly in the ground or in a buried duct are for a limited number of installation
conditions. Where analytical methods are not available for calculation of external thermal
resistance finite element methods may be used. Guidance on the use of finite element
methods for calculating cable current ratings is given in IEC TR 62095.dition 2.0 2015-04 INTERNATIONAL STANDARD NORME INTERNATIONALE Electric cables – Calculation of the current rating – Part 2-1: Thermal resistance – Calculation of thermal resistance Cables électriques – Calcul du courant admissible – Partie 2-1: Résistance thermique – Calcul de la résistance thermique IEC 60287-2-1:2015-04(en-fr) THIS PUBLICATION IS COPYRIGHT PROTECTED Copyright ? 2015 IEC, Genev