This part of IEC 60331 specifies the test method for cables which are required to maintain
circuit integrity when subject to fire and mechanical shock under specified conditions.
This document is applicable to cables of rated voltage not exceeding 600 V/1 000 V, including
those of rated voltage below 80 V, metallic data and telecom cables and optical fibre cables.
It is intended for use when testing cables of not greater than 20 mm overall diameter.
Cables of larger diameter are intended to be tested using the apparatus, procedure and
requirements of IEC 60331-1.
This document includes details for the specific point of failure, continuity checking
arrangement, test sample, test procedure and test report relevant to electric power and
control cables with rated voltage up to and including 600 V/1000 V. Details for the specific
point of failure, continuity checking arrangement, test sample, test procedure and test report
relevant to metallic data and telecom cables and optical fibre cables are not given by
IEC 60331-2.
Although the scope is restricted to cables with rated voltage up to and including 0,6/1,0 kV,
the procedure can be used, with the agreement of the manufacturer and the purchaser, for
cables with rated voltage up to and including 1,8/3 (3,3) kV, provided that suitable fuses are
used.
Annex A provides the method of verification of the burner and control system used for the
test.
Requirements are stated for an identification that may optionally be marked on the cable to
signify compliance with this standard.
CAUTION – The test given in this standard may involve the use of dangerous voltages
and temperatures. Suitable precautions should be taken against the risk of shock,
burning, fire and explosion that may be involved, and against any noxious fumes that
may be produced.dition 2.0 2018-03
INTERNATIONAL
STANDARD
GROUP SAFETY PUBLICATION
Tests for electric cables under fire conditions – Circuit integrity –
Part 2: Test method for fire with shock at a temperature of at least 830 °C for
cables of rated voltage up to and including 0,6/1,0 kV and with an overall
diameter not exceeding 20 mm
IEC 60331-2:2018-03(en)
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright ? 2018 IEC
-
GB 30871-2022免费下载危险化学品企业特殊作业安全规范 2023-07-06
-
GB/T 1094.1-2013电力变压器 第1部分:总则 2023-07-06
-
GB/T 706-2016热轧型钢 2023-07-06
-
GB 9706.1-2020医用电气设备 第1部分:基本安全和基本性能的通用要求 2023-07-06
-
JB/T 10216-2013电控配电用电缆桥架 2023-07-06
-
GB/T 10801.2-2018绝热用挤塑聚苯乙烯泡沫塑料(XPS) 2023-07-06
-
GB 51251-2017建筑防烟排烟系统技术标准 2023-07-06
-
JTG D20-2017公路路线设计规范 2023-07-06